OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
346209059 0418300 2022-08-31 240 STADIUM WAY, MADISON, AL, 35758
Inspection Type Prog Related
Scope Partial
Safety/Health Safety
Close Conference 2023-03-01
Emphasis N: CTARGET, P: CTARGET
Case Closed 2023-04-04

Related Activity

Type Inspection
Activity Nr 1621273
Safety Yes
Type Inspection
Activity Nr 1620840
Safety Yes
Type Inspection
Activity Nr 1620363
Safety Yes
Type Inspection
Activity Nr 1620988
Safety Yes
Type Inspection
Activity Nr 1620465
Safety Yes

Violation Items

Citation ID 01001A
Citaton Type Serious
Standard Cited 19261052 B01
Issuance Date 2023-03-02
Current Penalty 870.6
Initial Penalty 1451.0
Final Order 2023-03-17
Nr Instances 1
Nr Exposed 4
Gravity 1
FTA Current Penalty 0.0
Citation text line 29 CFR 1926.1052(b)(1): Foot traffic was not prohibited on stairways where the treads and/or landings of pan stairs were to be filled in with concrete or other material at a later date and stairs were not temporarily fitted with wood or other solid material at least to the top edge of each pan: (a) On or about August 31, 2022 - 240 Stadium Way, Madison, AL, employees were exposed to trip hazards when the boards used to fill the pan were approximately 3/8 inch lower than the lip of the pan.
Citation ID 01001B
Citaton Type Serious
Standard Cited 19261052 B02
Issuance Date 2023-03-02
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2023-03-17
Nr Instances 1
Nr Exposed 4
Gravity 1
FTA Current Penalty 0.0
Citation text line 29 CFR 1926.1052(b)(2): Foot traffic was not prohibited on skeleton metal stairs where permanent treads and/or landings were to be installed at a later date and the stairs were not fitted with secured temporary treads and/or landings long enough to cover the entire tread or landing area: (a) On or about August 31, 2022 - 240 Stadium Way, Madison, AL, employees were exposed to trip hazards when the boards used to fill the pan did not cover the entire tread area.