Search icon

Mount Vernon Chemicals LLC

Details

Name: Mount Vernon Chemicals LLC
Jurisdiction: Alabama
Legal type: Foreign Limited Liability Company
Status: Exists
Date of registration: 30 Nov 2007 (17 years ago)
Entity Number: 000-614-710
Register Number: 000614710
ZIP code: 36104
County: Montgomery
Place of Formation: South Carolina
Principal Address: 503 S MAIN STMAULDIN, SC 29662
Registered Office Street Address: 2 NORTH JACKSON STREET SUITE 605MONTGOMERY, AL 36104

Activities CHEMICAL MFG

Agent

Name Role
COGENCY GLOBAL INC Agent

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
341863140 0418600 2016-10-25 2905 HIGHWAY 280 EAST, OPELIKA, AL, 36804
Inspection Type Complaint
Scope Partial
Safety/Health Safety
Close Conference 2016-10-25
Case Closed 2017-10-24

Related Activity

Type Complaint
Activity Nr 1147315
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19100132 A
Issuance Date 2017-03-21
Abatement Due Date 2017-04-13
Current Penalty 5000.0
Initial Penalty 7243.0
Final Order 2017-04-11
Nr Instances 1
Nr Exposed 2
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: (a) Reactor area - Employees exposed to thermal energy hazards from steam pipes that are not insulated. The employees are not provided with thermal protection of the extremities and face to protected them from the thermal energy of hot steam pipes. (b) Reactor area - Employees exposed to thermal energy hazards from steam pipes and jackets that are leaking. The employees are not provided with thermal protection of the extremities and face to protected them from the steam leaks on the 2000 gallon reactor and the new 4000 gallon reactor.
Citation ID 01002
Citaton Type Serious
Standard Cited 19100305 J02 V
Issuance Date 2017-03-21
Abatement Due Date 2017-04-13
Current Penalty 5000.0
Initial Penalty 7243.0
Final Order 2017-04-11
Nr Instances 2
Nr Exposed 1
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered. a) On October 25, 2016 the electrical outlets in the quality control laboratory that are with-in 16 inches of the water sink were not have an enclosure or protected with a ground fault circuit-interrupter for personnel in accordance with the National Electric Code NFPA 70-1999 Article 210-8. b) On October 25, 2016 the electrical outlets in the employee break room that are with-in 29 inches of the water sink were not have an enclosure or protected with a ground fault circuit-interrupter for personnel in accordance with the National Electric Code NFPA 70-1999 Article 210-8.
Citation ID 01003
Citaton Type Serious
Standard Cited 19100303 G01
Issuance Date 2017-03-21
Abatement Due Date 2017-04-13
Current Penalty 3470.0
Initial Penalty 7243.0
Final Order 2017-04-11
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) On October 25, 2016 the electrical panel containing circuit breakers in the office space adjacent to the quality control laboratory area was obstructed with an office desk located in front of the panel.
Citation ID 01004
Citaton Type Serious
Standard Cited 19100305 J02 VII
Issuance Date 2017-03-21
Abatement Due Date 2017-04-13
Current Penalty 5000.0
Initial Penalty 9054.0
Final Order 2017-04-11
Nr Instances 1
Nr Exposed 1
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.305(j)(2)(vii): A receptacle installed in a wet location where the product intended to be plugged into it was to be attended while in use did not have an enclosure that was weatherproof when the attachment plug cap was removed: (a) Reactors Area - The 120 volt electric outlet box between the new 4000 gallon reactor and the 5000 gallon reactor is not approved for the location due to water coming down from the mezzanine area.

Date of last update: 15 Aug 2024

Sources: Alabama Secretary of State