Name: | Mount Vernon Chemicals LLC |
Jurisdiction: | Alabama |
Legal type: | Foreign Limited Liability Company |
Status: | Exists |
Date of registration: | 30 Nov 2007 (17 years ago) |
Entity Number: | 000-614-710 |
Register Number: | 000614710 |
ZIP code: | 36104 |
County: | Montgomery |
Place of Formation: | South Carolina |
Principal Address: | 503 S MAIN STMAULDIN, SC 29662 |
Registered Office Street Address: | 2 NORTH JACKSON STREET SUITE 605MONTGOMERY, AL 36104 |
Activities
CHEMICAL MFG
Name | Role |
---|---|
COGENCY GLOBAL INC | Agent |
Inspection Nr | Report ID | Date Opened | Site Address | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
341863140 | 0418600 | 2016-10-25 | 2905 HIGHWAY 280 EAST, OPELIKA, AL, 36804 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Type | Complaint |
Activity Nr | 1147315 |
Safety | Yes |
Violation Items
Citation ID | 01001 |
Citaton Type | Serious |
Standard Cited | 19100132 A |
Issuance Date | 2017-03-21 |
Abatement Due Date | 2017-04-13 |
Current Penalty | 5000.0 |
Initial Penalty | 7243.0 |
Final Order | 2017-04-11 |
Nr Instances | 1 |
Nr Exposed | 2 |
Related Event Code (REC) | Complaint |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: (a) Reactor area - Employees exposed to thermal energy hazards from steam pipes that are not insulated. The employees are not provided with thermal protection of the extremities and face to protected them from the thermal energy of hot steam pipes. (b) Reactor area - Employees exposed to thermal energy hazards from steam pipes and jackets that are leaking. The employees are not provided with thermal protection of the extremities and face to protected them from the steam leaks on the 2000 gallon reactor and the new 4000 gallon reactor. |
Citation ID | 01002 |
Citaton Type | Serious |
Standard Cited | 19100305 J02 V |
Issuance Date | 2017-03-21 |
Abatement Due Date | 2017-04-13 |
Current Penalty | 5000.0 |
Initial Penalty | 7243.0 |
Final Order | 2017-04-11 |
Nr Instances | 2 |
Nr Exposed | 1 |
Related Event Code (REC) | Complaint |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered. a) On October 25, 2016 the electrical outlets in the quality control laboratory that are with-in 16 inches of the water sink were not have an enclosure or protected with a ground fault circuit-interrupter for personnel in accordance with the National Electric Code NFPA 70-1999 Article 210-8. b) On October 25, 2016 the electrical outlets in the employee break room that are with-in 29 inches of the water sink were not have an enclosure or protected with a ground fault circuit-interrupter for personnel in accordance with the National Electric Code NFPA 70-1999 Article 210-8. |
Citation ID | 01003 |
Citaton Type | Serious |
Standard Cited | 19100303 G01 |
Issuance Date | 2017-03-21 |
Abatement Due Date | 2017-04-13 |
Current Penalty | 3470.0 |
Initial Penalty | 7243.0 |
Final Order | 2017-04-11 |
Nr Instances | 1 |
Nr Exposed | 1 |
Related Event Code (REC) | Complaint |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) On October 25, 2016 the electrical panel containing circuit breakers in the office space adjacent to the quality control laboratory area was obstructed with an office desk located in front of the panel. |
Citation ID | 01004 |
Citaton Type | Serious |
Standard Cited | 19100305 J02 VII |
Issuance Date | 2017-03-21 |
Abatement Due Date | 2017-04-13 |
Current Penalty | 5000.0 |
Initial Penalty | 9054.0 |
Final Order | 2017-04-11 |
Nr Instances | 1 |
Nr Exposed | 1 |
Related Event Code (REC) | Complaint |
Gravity | 5 |
FTA Current Penalty | 0.0 |
Citation text line | 29 CFR 1910.305(j)(2)(vii): A receptacle installed in a wet location where the product intended to be plugged into it was to be attended while in use did not have an enclosure that was weatherproof when the attachment plug cap was removed: (a) Reactors Area - The 120 volt electric outlet box between the new 4000 gallon reactor and the 5000 gallon reactor is not approved for the location due to water coming down from the mezzanine area. |