Search icon

Nordic Logistics and Warehousing, LLC

Details

Name: Nordic Logistics and Warehousing, LLC
Jurisdiction: Alabama
Legal type: Foreign Limited Liability Company
Status: Exists
Date of registration: 10 Jun 2011 (14 years ago)
Entity Number: 000-014-368
Register Number: 000014368
ZIP code: 36104
County: Montgomery
Place of Formation: Delaware
Principal Address: 4300 PLEASANTDALE ROADATLANTA, GA 30340
Registered Office Street Address: 641 SOUTH LAWRENCE STREETMONTGOMERY, AL 36104

Agent

Name Role
CORPORATION SERVICE COMPANY, INC. Agent

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
335748992 0418300 2012-08-13 670 AIRPORT ROAD, OXFORD, AL, 36203
Inspection Type Planned
Scope Partial
Safety/Health Health
Close Conference 2012-11-13
Emphasis L: EISAX, L: EISAOF, N: CHEMNEP, P: CHEMNEP
Case Closed 2012-12-11

Related Activity

Type Inspection
Activity Nr 576378
Health Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19100119 D03 II
Issuance Date 2012-11-26
Current Penalty 2550.0
Initial Penalty 4250.0
Final Order 2012-12-21
Nr Instances 1
Nr Exposed 2
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) On or about August 13, 2012 - Cold Storage Facility, the ammonia refrigeration machine room did not have a safety shower and eye wash unit located external to the machine room and readily accessible to employees as specified in ANSI/IIAR Standard 2-2008, Section 13.3.1.4.
Citation ID 01002
Citaton Type Serious
Standard Cited 19100119 F01 III B
Issuance Date 2012-11-26
Abatement Due Date 2012-12-06
Current Penalty 2550.0
Initial Penalty 4250.0
Final Order 2012-12-21
Nr Instances 1
Nr Exposed 2
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.119(f)(1)(iii)(B): The employer written operating procedures did not address the precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment: (a) On or about August 13, 2012 - Cold Storage Facility, Ammonia Machine Room, the operating procedure for Draining Oil From Oil Pot did not require and emphasize the use of air-purifying respirators with ammonia canisters.

Date of last update: 30 Jul 2024

Sources: Alabama Secretary of State